KSB DeltaBasic

Pressure booster system

Fully automatic pressure booster system with two to three (MVP) / four (SVP) vertical high-pressure pumps in two variable speed versions.

The MVP and SVP variable speed versions ensure variable speed control of each pump by motor-mounted frequency inverter for asynchronous motors (MVP) or by PumpDrive variable speed system and KSB SuPremE motor (SVP), respectively, providing fully electronic control to ensure the required supply pressure.

Equipped with a central fuse box.

Pressure boosting

KSB DeltaBasic

Key information

Datasheets

Technical data

Key information

  • Energy-efficient
    • The pressure booster system is equipped with KSB SuPremE IE5Product benefits synchronous reluctance motors (for the SVP variant).
    • Speed control ensures energy-efficient operation and constant pressure.
  • Service-friendly
    • The innovative length-adjustable lift check valve allows maintenance work to be carried out without interrupting the water supply.
  • Easy to operate
    • The ready-to-connect, pre-assembled and tested system makes for fast and straightforward commissioning.
    • The manifold position can be changed easily at the place of installation.
  • Space-saving
    • The compact design makes for a small footprint.
  • Long service life
    • The powder-coated baseplate and stainless steel hydraulic components provide a high level of corrosion resistance.
  • Reliable and safe
    • Integrated dry running protection ensures reliable operation.
    • Zero dead volume in the piping and optimum flushing of add-on parts provide protection against legionella.
  • Suitable for drinking water
    • The system components are suitable for drinking water, and the systems are certified to the relevant applicable drinking water standards.
  • Efficiency classes to IEC TS 60034-30-2:2016
KSB DeltaBasic

Datasheets

Download the KSB datasheet

DeltaBasic

Download →

Technical data

Connection type: External-thread connection, Flange
Drive concept: Electric actuator
Max. flow rate: 65.4 m3/h
Min. flow rate: 0.2 m3/h
Max. head: 134 m
Min. head: 13 m
Function Intg software Ctrl ut: Control
Mains frequency: 50 Hz

Mains voltage: 400 V
Casing material: 1.4308
Nominal pressure: PN 16
Max. allowed working pressure: 16 bar
Suction behaviour: Non-self-priming
Maximum allowable fluid temperature: 60 °C
Minimum allowable fluid temperature: 0 °C